+98 21 8875 2014 info@moghancableco.com

 

Wire Armoured Power Cables

Hits: 1755
WIRE ARMOURED XLPE MV POWER CABLES U0/U(Um)=36/63(72.5)KV
                           
        Single Core      N2XSYRY/ NA2XSYRY      
 
  • Standards:   IEC 60840
                         VDE 0276-632
     
  • Construction:    
    CU or AL/SCT/SC/XLPE/SC/SCT(WB)/CWS/PET/PVC(Bd)/AWA/PVC
                                                                                                                                 

                   Stranded & Compacted Copper or Aluminium Conductor
                   Semi-conducting tape
                   Innner Semi-Conducting Compound
                   Dry Cured XLPE Insulation (Dry curing/Dry cooling, Dry: Nitrogen gas) 
                   Outer Semi-Conducting Compound
                   Water blocking Semi-Conducting tape
                   Copper Wire Screen + Equalizing Cu Tape applied helically
                   Polyester tape
                   Separation PVC Sheath 
                   AL Wire Armour
                   PVC outer sheath (HDPE, Halogen free and low smoke, Chemical resistant, Low smoke PVC, Anti rodent PVC outer sheath is also available on request)

 

 

CONSTRUCTIONAL& DESIGN DATA
 
Conductor & Screen Nominal
Cross Section
Conductor Diameter
Insulation Thickness
Approx. Diameter Over Insulation
Armor Wire Diameter
Sheath Thickness
Approx. Overall Diameter 
No. × mm²
mm
mm
mm
mm
mm mm
1x185       RM/25 16 10.5 39 2.5 2.8 58
1x240       RM/25 18.4 10.5 42 3.15 2.9 62 
1x300       RM/25 20.5 10.5 44 3.15 3.0 64 
1x400       RM/35 23.3 10.5 47 3.15 3.1 67 
1x500       RM/50 26.5 10.5 50 3.15 3.2 71 
1x630       RM/50 30.2 10.5 54 3.15 3.4 75 
1x800       RM/50 34.5 10.5 58 3.15 3.5 80 
1x1000     RM/50 39 10.5 63 3.15 3.7 85 
1x1200     RM/50 42 10.5 66 3.15 3.8 88 
 
Max. conductor temperature continuous operation : 90° C
Max. conductor temperature in short circuit : 250° C